Tests
6
first: No Insulation
Rw range
8–25dB
spread 17 dB
Highest Rw
25dB
GW 90 mm R2.7
Largest ΔRw vs first
+16dB
GW 90 mm R2.7
Sound reduction index (R)
R′ from the B&K 2270, re-referenced to the 0.9216 m² specimen area (−0.35 dB; −10.96 dB for the 22 Sep tests, logged with S = 11.5 m²). Grey lines: the open aperture (the opening with nothing in it) and unperforated 10 mm plasterboard.
Single-number ratings
Open in explorer- No InsulationC 0 · Ctr 0 · vs open +8 · mean R 8.68 dBfirst
- GW 45 mm R2.5C 0 · Ctr −1 · vs open +14 · mean R 13.214 dB+6
- GW 90 mm R2.5C −1 · Ctr −3 · vs open +19 · mean R 17.520 dB+11
- GW 90 mm R2.7C −1 · Ctr −4 · vs open +24 · mean R 23.225 dB+16
- GW 100 mm R5C −1 · Ctr −2 · vs open +16 · mean R 14.917 dB+8
- GW 175 mm R3.5C 0 · Ctr −2 · vs open +19 · mean R 17.119 dB+11
| Listen | Varies | Rw | C | Ctr | ΔRw vs first | ΔRw vs open | Mean R | |
|---|---|---|---|---|---|---|---|---|
| No Insulation | 8 | 0 | 0 | ref. | +8 | 8.6 | ||
| GW 45 mm R2.5 | 14 | 0 | −1 | +6 | +14 | 13.2 | ||
| GW 90 mm R2.5 | 20 | −1 | −3 | +11 | +19 | 17.5 | ||
| GW 90 mm R2.7 | 25 | −1 | −4 | +16 | +24 | 23.2 | ||
| GW 100 mm R5 | 17 | −1 | −2 | +8 | +16 | 14.9 | ||
| GW 175 mm R3.5 | 19 | 0 | −2 | +11 | +19 | 17.1 |
Right: Rw, and below it ΔRw against the first test. Rw, C and Ctr per ISO 717-1 over 100–3150 Hz. ΔRw fits the reference curve to R − R(open aperture); ΔRw vs first is the difference between a test's ΔRw and the first test's, as the report quotes changes, so it can differ by a decibel from the change in Rw. Mean R is the arithmetic mean over the 16 rating bands.