Tests
2
first: No MLV
Rw range
19–31dB
spread 12 dB
Highest Rw
31dB
MLV
Largest ΔRw vs first
+11dB
MLV
Sound reduction index (R)
R′ from the B&K 2270, re-referenced to the 0.9216 m² specimen area (−0.35 dB; −10.96 dB for the 22 Sep tests, logged with S = 11.5 m²). Grey lines: the open aperture (the opening with nothing in it) and unperforated 10 mm plasterboard.
Single-number ratings
Open in explorer- No MLVC −1 · Ctr −3 · vs open +19 · mean R 19.219 dBfirst
- MLVC −2 · Ctr −6 · vs open +30 · mean R 28.631 dB+11
Right: Rw, and below it ΔRw against the first test. Rw, C and Ctr per ISO 717-1 over 100–3150 Hz. ΔRw fits the reference curve to R − R(open aperture); ΔRw vs first is the difference between a test's ΔRw and the first test's, as the report quotes changes, so it can differ by a decibel from the change in Rw. Mean R is the arithmetic mean over the 16 rating bands.