Perforated Panel Acoustics

Effect of flow resistivity

Plasterboard Slots, No MLV

Insulation comparisons keyed on measured airflow resistivity.

Tests

6

first: No Insulation

Rw range

9–25dB

spread 16 dB

Highest Rw

25dB

GW 90 mm R2.7 (26,400 N·s/m⁴)

Largest ΔRw vs first

+17dB

GW 90 mm R2.7 (26,400 N·s/m⁴)

Sound reduction index (R)

R′ from the B&K 2270, re-referenced to the 0.9216 m² specimen area (−0.35 dB; −10.96 dB for the 22 Sep tests, logged with S = 11.5 m²). Grey lines: the open aperture (the opening with nothing in it) and unperforated 10 mm plasterboard.

Single-number ratings

Open in explorer
ListenVariesRwCCtrΔRw vs firstΔRw vs openMean R
No Insulation
9
00ref.+89.1
GW 100 mm R5 (9,600 N·s/m⁴)
18
−1−3+9+1715.6
GW 175 mm R3.5 (10,200 N·s/m⁴)
20
−1−3+11+1917.4
GW 45 mm R2.5 (14,800 N·s/m⁴)
15
0−1+7+1513.9
GW 90 mm R2.5 (17,100 N·s/m⁴)
20
0−2+12+2018.4
GW 90 mm R2.7 (26,400 N·s/m⁴)
25
0−3+17+2524.2

Right: Rw, and below it ΔRw against the first test. Rw, C and Ctr per ISO 717-1 over 100–3150 Hz. ΔRw fits the reference curve to R − R(open aperture); ΔRw vs first is the difference between a test's ΔRw and the first test's, as the report quotes changes, so it can differ by a decibel from the change in Rw. Mean R is the arithmetic mean over the 16 rating bands.